X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA

Ask Latest Price
Video Channel
Brand Name :B&R
Model Number :X20AO4622
Certification :COC
Place of Origin :Austria
MOQ :1EA
Price :USD
Payment Terms :T/T
Supply Ability :10EA
Delivery Time :3-5 DAYS
Packaging Details :Original
Product Name :B&R
Product Model :X20AO4622
Product Type :I/O module
ID code :0x1BA3
Internal I/O :1.8 W (Rev. ≥ J0), 2.2 W (Rev. < J0)
Warranty :1 Year
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA

MATERIAL NUMBER: X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA

X20AO4622

DESCRIPTION:
  • 4 analog outputs
  • Either current or voltage signal possible
  • 13-bit digital converter resolution

X20 analog output module, 4 outputs, 10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution

General information
B&R ID code 0x1BA3
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Channel type Yes, using software
Power consumption
Bus 0.01 W
Internal I/O 1.8 W (Rev. ≥ J0), 2.2 W (Rev. < J0)
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B(0 - 55°C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck)
LR ENV1
KR Yes
ABS Yes
EAC Yes
KC Yes
Analog outputs
Output ±10 V or 0 to 20 mA / 4 to 20 mA, via different terminals
Max. output current 10 mA at voltage >5 V
15 mA at voltage <5 V
Digital converter resolution
Voltage ±12-bit
Current 12-bit
Conversion time 300 µs for all outputs
Settling time on output change over entire range 500 µs
Switch on/off behavior Internal enable relay for startup
Max. error
Voltage
Gain 0.08%
Offset 0.05%
Current
Gain 0.09%
Offset 0.05%
Output protection Short-circuit proof
Output format
Voltage INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
Current INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Load per channel
Voltage Max. ±10 mA, load ≥1 kΩ
Current Load max. 600 Ω (Rev. ≥ J0), 500 Ω (Rev. < J0)
Short-circuit proof Current limiting ±40 mA
Output filter First-order low-pass filter / cutoff frequency 10 kHz
Max. gain drift
Voltage 0.015%/°C
Current 0.02 %/°C
Max. offset drift
Voltage 0.032%/°C
Current 0.032%/°C
Error caused by load change
Voltage Max. 0.11%, from 10 MΩ → 1 kΩ, resistive
Current Max. 0.5%, from 1 Ω → 600 Ω, resistive
Nonlinearity <0.007%
Insulation voltage between channel and bus 500 Veff
Electrical properties
Electrical isolation Channel isolated from bus
Channel not isolated from channel
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C (Rev. ≥ J0), 0 to 55°C (Rev. < J0)
Vertical mounting orientation -25 to 50°C (Rev. ≥ J0), 0 to 50°C (Rev. < J0)
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.
Pitch 12.5+0.2mm
Inquiry Cart 0